液冷服务器保压设备

Liquid cooling server pressure maintaining equipment

Suitable for online airtightness testing of server nodes and cabinets, using high-precision airtightness testers, integrating air source temperature, pressure, temperature and humidity monitoring functions, equipped with a two-stage filtering system to ensure the safety and reliability of the air source entering the node. This product can meet the simultaneous detection of four nodes, with a simple structure, high integration, high instrument accuracy, and good reliability.
Contact Us

Product Details

Suitable for online airtightness testing of server nodes and cabinets, using high-precision airtightness testers, integrating air source temperature, pressure, temperature and humidity monitoring functions, equipped with a two-stage filtering system to ensure the safety and reliability of the air source entering the node. This product can meet the simultaneous detection of four nodes, with a simple structure, high integration, high instrument accuracy, and good reliability.

 

 

 

Features:

 

 

  • Perform airtightness testing on four nodes simultaneously or separately
  • The accuracy of airtightness detection can reach 0.1kpa
  • Equipped with automatic voltage stabilization and regulation functions
  • The holding pressure, holding time, and leakage parameters can be flexibly set
  • Equipped with a 21 inch display screen, easy to read data and set parameters
  • Equipped with an alarm mechanism to assist operation and maintenance personnel in quickly and accurately locating system anomalies

 

 

 

 

Application:

 

 

  • Air tightness detection of liquid cooled server nodes
  • Air tightness testing of liquid cooled cabinet

 

 

 

Item

Parameters

System design parameters

Detection medium type

Clean and dry compressed air

Air source regulation pressure

≤0.7Mpa 【 Settable 】

Filtration

Filter 1 < 0.3 μ M/Filter 2 < 0.01 μ M

Charging time

20s【 Settable 】

Holding time

≤10min【 Settable 】

Pressure holding pass criterion

≤4.16E-3 m bar.L/s

Channel configuration and accuracy of airtightness detector

Four channel detection/0.1 kPa

Max. power consumption

≤0.25 kW

Power

3P AC380V 50Hz

Design pressure (PSI/bar)*2

102/6

Test pressure (PSI/bar)

102/7

Weight (kg/lbs)

480/1058

Working environment temperature and humidity

-20~45℃/ RH5~85%

Storage environment temperature and humidity

-40~65℃/RH5~95%

Interface specifications

Chuck/quick connect

Power interface

Aviation connector WS40J5Z, 5-core

Communication interfaces and quantity

RJ45

Modbus

Modbus TCP/IP

Noise

60dB(A)

Color

Pantone Cold Grey C11

External dimensions

(height * width * depth)

1490x800x1400mm

 

Product Classification