液冷服务器注液清洗设备

Liquid cooling server cleaning & injection equipment

Before conducting water supply management and overall testing on server cabinets, the liquid cooling channels inside the cabinets should be filled with liquid, and the liquid cooling circuits inside the cabinets should be flushed. This can be used to fill and flush four cabinets and two nodes. The equipment integrates turbidity, pH, and conductivity for water quality detection, ensuring that the water entering the tested equipment is pure and highly clean.
Contact Us

Product Details

Before conducting water supply management and overall testing on server cabinets, the liquid cooling channels inside the cabinets should be filled with liquid, and the liquid cooling circuits inside the cabinets should be flushed. This can be used to fill and flush four cabinets and two nodes. The equipment integrates turbidity, pH, and conductivity for water quality detection, ensuring that the water entering the tested equipment is pure and highly clean; Adopting a dual pump configuration and variable frequency control, high reliability; This product can be tested simultaneously through multiple channels, with fast efficiency, high structural integration, and high detection accuracy.

 

 

 

Features:

 

 

  • Perform airtightness testing on four nodes simultaneously or separately
  • Rapid detection of water quality pH, turbidity, and conductivity
  • SUS304 stainless steel pipeline has high pressure bearing capacity and high reliability
  • The parameters of flow rate, injection time, and flushing time can be flexibly set
  • Equipped with a 21 inch display screen, easy to read data and set parameters
  • Equipped with an alarm mechanism to assist operation and maintenance personnel in quickly and accurately locating system anomalies

 

 

 

 

Application:

 

 

  • Liquid cooling server node injection and cleaning
  • Liquid cooling cabinet filling and cleaning

 

 

 

 

Item

Parameters

System design parameters

Detection medium type

Pure water

Water quality requirements

Inflow water quality: Conductivity < 3 μ S/cm, pH between 5-7.5, turbidity<3NTU;

Inflow water quality: Conductivity < 10μ S/cm, pH between 5-7.5, turbidity<10NTU;

Cabinet capacity

≤7.5(L/cabinet)【 Settable 】

Injection time

≤5(min)【 Settable 】

Flushing time

≤2(min)【 Settable 】

Liquid injection judgment

Monitor the set time to determine if it is fully filled

Filter accuracy

≤50μm

Max. power consumption

0.8kW

Power

3P AC380V 50Hz

Design pressure (PSI/bar)*2

116/8

Test pressure (PSI/bar)

145/10

Weight (kg/lbs)

800/1764

Working environment temperature and humidity

-20~45℃/ RH5~85%

Storage environment temperature and humidity

-40~65℃/RH5~95%

Interface specifications

Chuck/quick connect

Power interface

Aviation connector

Communication interfaces and quantity

RJ45/6

Modbus

Modbus TCP/IP

Noise

60dB(A)

Color

Pantone Cold Grey C11

External dimensions (height * width * depth)

1490x800x1400mm

 

 

 

 

Product Classification