Optical module cold plate
The cold plate of the optical module adopts liquid cooling technology. The cold plate is specially designed and arranged on the surface of the optical module. The heat generated during the operation of the optical module is carried away by the internal low-temperature liquid, which can be used to solve the heat dissipation problem of high-power optical modules in switch products and improve the uniformity of surface temperature between each optical module.
The cold plate of the optical module adopts liquid cooling technology. The cold plate is specially designed and arranged on the surface of the optical module. The heat generated during the operation of the optical module is carried away by the internal low-temperature liquid, which can be used to solve the heat dissipation problem of high-power optical modules in switch products and improve the uniformity of surface temperature between each optical module.
Features:
- Copper cold plate with high thermal conductivity
- Integrated brazing process with high reliability
- Special structure and flow channel design, low thermal resistance, high heat dissipation efficiency
Item | Description | Optical module cold plate |
Main performance parameters | Thermal design power consumption (W) | 25W*14 |
Design pressure (bar) | 2.75 | |
Cold plate material | Purple copper T2 | |
Pipe material | Purple copper TP2 | |
Medium | PG25 | |
Supply liquid temperature (℃) | 40 | |
Supply fluid flow rate (LPM) | 1.2 | |
Flow resistance (kPa) | 25.4 | |
Thermal resistance (℃/W) | ≤0.02 | |
Heat-conducting medium | Thermal pad,6.0 W/m·K | |
Size of thermal conductive medium | 58*23.5*0.5mm 54.5*11.2*0.5mm |
|
Structure parameters | Installation method | T15 Spring screw |
Surface treatment | Passivation | |
Flow path form | Series connection | |
External dimensions of single cold plate W * D * H (mm) | 552*59.3*59.2 | |
External interface | UQD02 male head |
-
ꄶ LIQUID COOLING
-
In Rack L2A CDU
-
In Row L2A Sidecar
-
In Rack L2L CDU
-
In Row L2L CDU
-
Rear door liquid cooling
-
Manifold
-
Liquid cooling loop
-
Immersion liquid cooling CDU&Tank
-
Liquid cooling cabinet
-
Liquid cooling EDU
-
Closed cooling tower
-
Mobile refill cart
-
Liquid cooling server pressure maintain
-
Server cleaning and injection equipment
-
Server drain-dry-nitrogen injection
-
Server test equipment transfer box
-
Cold plate thermal performance testing
-
Water purifier
-
-
ꄶ HEAT EXTRACTION
-
ꄶ FLUID CONTROL COMPONENT
-
ꄶ AIR COOLING
-
ꄶ HEATER