image

Immersion liquid cooled tank

CDU provides power through a circulating pump to overcome the resistance along the way, continuously pumping the high-temperature medium in Tank into the heat exchanger at a constant pressure and flow rate, exchanging heat with the primary cooling medium, and exporting the heat to the ambient air. After cooling, the cooling medium is uniformly supplied to the tank through the supply pipe.
Contact Us

Product Details

CDU provides power through a circulating pump to overcome the resistance along the way, continuously pumping the high-temperature medium in Tank into the heat exchanger at a constant pressure and flow rate, exchanging heat with the primary cooling medium, and exporting the heat to the ambient air. After cooling, the cooling medium is uniformly supplied to the tank through the supply pipe. The cooling medium flows through the heating element of the exchange in the tank, guiding the heat of the heating element into the cooling medium. The heated medium flows into the return pipeline, flows out of Tank, and enters the return port of the circulation pump, forming a complete circulating cooling circuit.

 


Features:

 

  • Rated cooling capacity 36kW
  • Inner liner SUS304 material, top observation window, visible solution status
  • The liquid receiving material meets the compatibility requirements of the solution
  • Integrated flow distribution board to ensure flow uniformity
  • Busbar centralized power supply, simple and beautiful
  • CDU can be either liquid or air liquid

 


Application:

 

  • Server cooling
  • Switch heat dissipation

 

 

Item Description Parameters
System design parameters Cooling capacity 36kW 
Tank capacity 52U
Server specifications 21 inches
Cooling medium Fluoride solution/silicone oil
Rated flow rate 12m³/h
Rated liquid supply temperature 35℃
Primary side cold source Cooling water at 8-25 ℃