液冷EDU

Liquid cooling EDU

The liquid cooled EDU integrates control, power, buffering, and heat exchange systems. It continuously pumps a constant pressure and flow of cooling medium into the supply side pipeline through a circulating pump. The cooling medium is evenly distributed to each rack through the machine room level manifold. The cooling medium flows through the server node to export heat and then converges to the return side pipeline.
Contact Us

Product Details

The liquid cooled EDU integrates control, power, buffering, and heat exchange systems. It continuously pumps a constant pressure and flow of cooling medium into the supply side pipeline through a circulating pump. The cooling medium is evenly distributed to each rack through the machine room level manifold. The cooling medium flows through the server node to export heat and then converges to the return side pipeline. The heat is exchanged with the cold air in the primary side machine room through the primary side CDU, and then exported to the machine room environment. Finally, the heat is exported to the external environment through the air conditioning in the data center machine room. The cooled cooling medium flows back to the circulation pump, is pressurized by the circulation pump, and then re-enters the supply side ring network pipeline, forming a closed circulating cooling circuit.

 

 

Features:

 

 

  • Platform based design, high integration, easy deployment and maintenance
  • Integrated pump drive function, providing primary circulation power
  • Integrated impurity filtration function to ensure system cleanliness
  • Integrated water quality management function, effectively ensuring the primary side water quality
  • Integrate voltage stabilization and constant pressure replenishment functions to reduce system operation and maintenance
  • Integrate group control functions and coordinate with the data center group control

 

 

 

Application:

 

  • Liquid cooled data center primary side

 

 

 

 

Item Parameters
System design parameters Rated cooling capacity 242kW 
Rated operating point 28.8m3/h
Design pressure 1.0MPa
Rated pressure 3P 380V 50/60Hz
System rated pressure 6.5kW
Internal circulation process design parameters Cooling medium PG-25
Rated liquid supply flow rate of the pump 28.8m3/h
Temperature difference between supply and return liquid 10℃
Design of liquid supply pump Single pump design, system level redundancy design
Secondary side pipeline Ring network design
Filtration ≤50μm
Static pressure of buffer tank ≤1.5 bar
External dimensions of CDU (width x depth x height) 800×1200×2100mm

 

 

 

 

 

 

 